Building factor: why an assembled transformer core loses more than the datasheet says

Technical articles

Technical articles ·

Building factor: why an assembled transformer core loses more than the datasheet says

Mill core loss is measured on single strips under ideal conditions. In a finished core, joints, cutting and clamping add loss. Knowing where it comes from helps designers choose grades and specify processing.

Every Baosteel CRGO grade carries a guaranteed maximum core loss, for example 0.90 W/kg at 1.7 T and 50 Hz for B27R090. That value is measured on prepared strips magnetised exactly along the rolling direction. A finished core never works under those ideal conditions, so its no-load loss per kilogram is higher. The ratio between the two is called the building factor.

Where the extra loss comes from

Joint design makes the biggest difference

Mitred joints keep the flux closer to the rolling direction than butt joints. Step-lap joints go further: by staggering the joint positions over several layers, the flux can pass each gap through neighbouring sheets. This is why step-lap designs are widely used in distribution and power transformers; they also tend to lower no-load current and noise.

What it means for grade selection

A better grade only pays off if the core is built well. Moving from a conventional grade to a domain-refined grade lowers the strip loss, but a core with high burrs or poorly fitted joints can lose much of that gain. When comparing offers, look at the guaranteed loss of the grade and at the processing behind it.